3. Depending on your choice, the following parameters appear (
#
= 1, 2 or 3, depending on the
value of
Select Output
):
•
Aout # Name
:
o
Aout 1
and
Aout 3
: Can be set to
Fire Rate
or
Other
.
o
Aout 2
: Can be set to
Valve
,
Fire Rate
or
Other
.
•
Aout # Signal
: Displays the signal for this output:
Aout 1
=
1-10v
,
Aout 2
and
Aout 3
: Appears only if
Select Output
=
Spare Analog Out 3
: A read-only
display of the signal associated with
Spare Analog Out 3
.
•
Aout # Min Fire Rate
and
Aout # Max Fire Rate
: Enter the minimum and
maximum fire rates. The analog voltage signal is linearly mapped to the firing rate
values. (Min Fire Rate Range: 0% to 50%, Max Fire Rate Range: 51% and 100%).
•
Rem Spr Aout # Add
: (Remote Spare Analog Output # Address, where
#
is the
output chosen in Step 2, 1, 2 or 3): Specify the address of the unit to which the
analog output signal is sent. (Range: 0 to 16)
6.5.4 Analog Inputs
Analog Input menu allows you to configure all available programmable analog inputs.
1. Go to:
Main Menu
→
Advanced Setup
→
Ancillary Device
→
Analog Inputs
.
Figure 6.5.4: Ancillary Device: Analog Inputs Screen
2. Choose the analog input you want to configure
. These inputs attach to the unit’s I/O box
strip J5, on the pins shown below.
•
Spare Analog In 1
– pin 3 Spare
Analog In 1+
pin 4
Spare Analog In 1-
•
Spare Analog In 2
– pin 5 Spare
Analog In 2+
pin 6
Spare Analog In 2-
•
Spare Analog In 3
– pin 1 Spare
Analog In 3+
pin 2
Spare Analog In 3-
3. Select the name for the input chosen in Step 2 in the
Name
field. (Note, the combination
chosen in Steps 2 and 3 determines what appears in
)
•
Not Assigned
•
Swing V1 Fdbk
•
Blr VSP Fdbk
•
SmartPlate VP
•
Remote Setpt 2
•
Swing V2 Fdbk
•
DHW VSP Fdbk
•
NOx