Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
101
of
196
2. The
Overwrite Calibration
screen now appears. Press
Yes
to overwrite the existing
combustion calibration. If you press
No
, the existing combustion calibration data is retained.
Figure 6.2.3.2-2: Unit: Load Settings Screen
3. The settings on the USB device are uploaded to the unit, overwriting the existing settings.
The
Restore Succeeded
screen appears if the restore was successfully, and the unit then
reboots in about 5 seconds. If there was a problem, the
Restore Failed
screen appears.
6.2.4 Fault Management
The
Fault Management
screen controls whether the reset mode for three fault conditions is
automatic or manual.
1. Go to:
Main Menu
→
Advanced Setup
→
Unit
→
Fault Management
.
Figure 6.2.4: Unit: Fault Management Screen
2. Choose the desired reset mode,
Manual
or
Automatic
, for all three fault conditions.
•
Power Reset
: Loss of electrical power.
•
Water Temp Reset
: Supply water temperature exceeds specified tolerance. This
applies only to the internal settings of the Controller,
not
to the Manual High Temp
Safely Limit switch.
•
Gas Pressure Reset
: Gas pressure exceeds or drops below specified tolerance
(model specific).