Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
156
of
196
6.6.1 AERtrim
The
AERtrim
screen provides access to AERtrim settings, O
2
Trim Parameters and AERtrim
status parameters. Note, the parameters in those screens are not available until AERtrim has
been successfully activated in the
AERtrim Settings
screen (see Section 6.6.2, below).
1. Go to:
Main Menu
→
Advanced Setup
→
Performance
→
AERtrim
.
Figure 6.6.1: Performance: AERtrim Screen
NOTE:
You can navigate from one
AERtrim
screen to the next in round-robin fashion using the
Page
Left
and
Page Right
icons on each screen.
AERtrim Settings
AERtrim functionality is enabled/disabled and configured on this unit from the
AERtrim
Settings
screen.
NOTES
:
AERtrim must be
activated
before it can be
enabled
. It is activated on all Benchmark Platinum
units before they are shipped. If a new controller is installed, it must be reactivated, which
requires entry of the Activation Code, created by AERCO specifically for each unit. This
process can be initiated from this screen, but you must have the Activation Code to complete
the process. Each Activation Code is based on the serial number of the unit, and is therefore
specific to that unit only. Once AERtrim has been successful activated, AERtrim can be
disabled and re-enabled without having to re-activate it.
AERtrim functionality is automatically disabled if the O
2
sensor is removed or faulted.