2. If you chose
Constant Setpoint
in step 1, specify the
SH
Setpoint
. When you press
Next
the
Other Operating Mode
screen appears (skip to Step 5).
Figure 2.3.2.2.3-3: BST Manager
– SH & Other: Space Heating Constant Setpoint
3. If you chose
Remote Setpoint
in step 1, the
Select Remote Setpoint Type
screen
appears. Choose how the unit will access the setpoint, then press
Next
.
Figure 2.3.2.2.3-4: BST Manager
– SH & Other: Select Remote Setpoint Type
A. If you chose
4-20mA
,
0-20mA
,
1-5V
, or
0-5V
, the
SH Analog Input
screen appears.
Enter the upper and lower limits of the SH setpoint in the
BST SH Setpt Low
Limit
and
BST SH Setpt High Limit
fields
.
When you press
Next
the
Other
Operating Mode
screen appears (skip to Step 5).
Figure 2.3.2.2.3-5: BST Manager
– SH & Other: SH Analog Input Screen
B. If you chose either
Network
or
BAS
, the
Other Operating Mode
screen appears
(skip to Step 5).