Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
113
of
196
Figure 6.2.7.4-1: Update Finished Screen
6. If there are updated
Graphics
,
I/O Board
or
Display
files, the associated button(s) will be
colored red (update required) or yellow (update recommended). Press all red and yellow
buttons to initiate the update; if you press more than one button, the Controller automatically
starts the next update when the previous update completes. During each update, the
associated button is greyed out. Do not remove the USB device until the
Update Finished
screen (Figure 6.2.7.4-1) appears.
Figure 6.2.7.4-2: Graphics Processing Screen
7. To ensure the firmware update was successful, you must now turn the
boiler’s power
OFF
and then back
ON
. Continue with the next step after restarting the boiler.
8. Once the Controller restarts, set the
Enable/Disable
switch back to
Enable
and remove the
USB device. If there was a problem with the update, see
9. Spot-check that the values recorded at the end of
are still in effect. This step
should be performed whether or not the firmware update was successful.
a.
Serial Number
and
Unit Type
in
Main Menu
→
Advanced Setup
→
Unit
→
Unit
Settings
.
b.
Combustion Calibration Summary
in
Main Menu
→
Calibration
→
Combustion
Summary
.
c.
Application Setup
, in
Main Menu
→
EZ Setup
. See summary in first screen, then
abort.
10. If the spot-check is successful, the process is complete. But if any of the settings changed,
or you suspect the setup was corrupted, complete the instructions in the next section,