Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
152
of
196
2. The following parameters Configure the
Remote Interlock
:
•
Remote Interlock Name
: Choose one of the following:
o
Flow
o
Damper
o
Louver
o
Other
•
Remote Intlk Use
: Specifies what will shut down if the selected interlock switch is
open, either the individual boiler or the full system. Choose
Sys Shutdown
or
Boiler
Shutdown
.
3. The following parameters configure the
Delayed Interlock
. This interlock includes an
adjustable delay timer, which delays the ignition sequence, allowing sufficient time for a
proving switch to be made to prevent a fault.
•
Delayed Interlock Name
: Choose one of the following:
o
Valve 1
o
Louver
o
Valve 2
o
Louver 2
•
Auxiliary Delay
: Select the interlock delay.
If the unit has a Sequencing Isolation
Valve,
this must be set to
120 seconds
(see
Benchmark PLATINUM-Edge:
Installation Manual (
OMM-0136, GF-210) Section 2.14:
BST Sequencing Isolation
Valve
).
(Range: 0 to 240 sec.)
6.5.2 Relays
The
Relays
screen gives you the ability to configure up to two auxiliary relays:
‘AUX 2’ Relay
and
‘PUMP 2’ Relay
.
1. Go to:
Main Menu
→
Advanced Setup
→
Ancillary Device
→
Relays
.
SELECT RELAY =
V2/Spare 1 Relay
SELECT RELAY =
Spare 2 Relay
Figure 6.5.2: Ancillary Devices: Auxiliary Relays Screens
2. Press
Select Relay
and choose either
V2/Spare 1 Relay
or
Spare 2 Relay
.
3. In the
Relay Name
parameter, choose the name for the relay selected above:
V2/Spare 1 Relay Names
Spare 2 Relay Names
•
Swing Valve 2
•
Summer Pump
•
Louver
•
Damper
•
System Pump
•
Pump 2
•
Louver 2
•
Sequenced Pump
•
System Pump
•
Pump 2
•
Louver 2
•
Sequenced Pump
•
Summer Pump
•
Louver
•
Damper
•
Other