Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
159
of
196
1. Go to:
Main Menu
→
Advanced Setup
→
Performance
→
AERtrim
→
AERtrim Status
.
Figure 6.6.1.3: AERtrim: AERtrim Status
2. This screen displays the following
“read only” parameters:
•
Auto Calibration Status
: The current Auto Calibration status.
•
Current Valve Position
: The A/F Valve
’s actual current position.
•
Target Valve Position
: The A/F Valve
’s target position.
•
O2
: The current O
2
level.
•
Current Blower Voltage
: The current blower voltage.
•
Target Blower Voltage
: The target voltage
•
Sensor Status
: The current status of the O
2
Sensor.
•
O2 Timer
: The current step in the AERtrim cycle.
3. Set the
O2 Monitoring
parameter to
Yes
or
No
. Yes enables the AERtrim function. When
set to
Yes
, the O
2
sensor is activated for 4 hours, followed by a 10 hours
“off” period.