Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
45
of
196
7. If you chose
Constant Setpoint
in Step 6, the
DHW Constant Setpoint
screen
appears. Specify the setpoint, then press
Next
and skip to Step 9.
Figure 2.3.2.2.1-10: BST Manager
– SH & DHW: DHW Constant Setpoint Screen
8. If you chose
Remote Setpoint
in step 6, the
Select Remote Setpoint Type
screen
appears. Choose how the unit will access the setpoint, then press
Next
.
Figure 2.3.2.2.1-11: BST Manager
– SH & DHW: Select Remote Setpoint Type
A. If you chose either
4-20mA
or
0-20mA
, the
DHW Analog Input
screen appears.
Configure the following parameters:
•
Choose the remote setpoint source in the
DHW Rmt Setpt Source
field
(the previous choice, if there was one, has a green border):
Spare Analog in
1
,
Spare Analog in 2
or
Spare Analog in 3
•
Enter the upper and lower limits of the DHW setpoint in the
DHW Setpt Low
Limit
and
DHW Setpt Hi Limit
fields.
•
Press
Next
to continue (skip to Step 9).
Figure 2.3.2.2.1-12: BST Manager
– SH & DHW: DHW Analog Input Screen