Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
22
of
196
3. If you chose
Remote Setpoint
in Step 1, the
Select Remote Setpoint Type
screen
appears. Choose how the unit will access the setpoint, then press
Next
.
Figure 2.2.1-4: Standalone
– Space Heating: Select Remote Setpoint Type Screen
A. If you chose
4-20mA
,
0-20mA
,
1-5V
or
0-5V
, the
SH Analog Input
screen appears.
Enter the upper and lower limits of the SH setpoint in the
Unit SH Setpt Low
Limit
and
Unit SH Setpt High Limit
fields
.
Pressing
Next
takes you to the
Select BAS Mode
instructions.
Figure 2.2.1-5: Standalone
– Space Heating: SH Analog Input Screen
B. If you chose
Network
, the
Comm Settings
screen appears. Enter the
Unit
Address
and
Unit Baud Rate
. Pressing
Next
takes you to the
Select BAS
Mode
Figure 2.2.1-6: Standalone
– Space Heating: Comm Settings Screen
C. If you chose either
BAS
or
PWM
, the
Select BAS Mode
screen appears; skip to