Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
103
of
196
2. Choose the
Unit Application
for this unit:
DHW
,
Other
or
SH
.
Unit Application = DHW
Unit Application = SH
Figure 6.2.6-1: Unit Application Configuration
3. Depending on the Application chosen above, one of five
Operating Modes
appears.
Choose the
Operating Mode
appropriate for the unit:
TABLE 6.1: Operating Modes
Available Operating Modes
Application
SH
DHW
Other
1 Constant Setpoint
✓
✓
✓
2 Remote Setpoint
✓
✓
✓
3 Direct Drive
✓
4 Combination
✓
5 Outdoor Reset
✓
4. Depending on the Application and Operating Mode chosen in Steps 2 and 3, a number of
additional parameters appear. The table below shows which parameters appear for each
combination of
Application
and numbered
Operating Mode
.
TABLE 6.2: Unit Application Configuration Parameters
Available Parameters
Unit Applications & Operating Modes
(see table above)
SH
DHW
Other
1
2
3
4
5
1
2
1
2
1
Unit SH Operating Mode
✓
✓
✓
✓
✓
2
Unit DHW Operating Mode
✓
✓
3
Unit Other Operating Mode
✓
✓
4
Unit SH Setpoint
✓
5
Remote Signal
✓
✓
✓
7
Unit Address
✓
✓
✓
✓
✓
✓
✓
✓
✓
8
Unit Baud Rate
✓
✓
✓
✓
✓
✓
✓
✓
✓
9
Unit DHW Setpoint
✓
✓
10 Analog Input Source
1
✓
✓
10 a Name
1
✓
✓
11 Unit DHW Remote Signal
✓