Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
49
of
196
•
Enter the upper and lower limits of the DHW setpoint in the
DHW Setpt Low
Limit
and
DHW Setpt Hi Limit
fields.
•
Pressing
Next
takes you to the
Other Operating Mode
screen (skip to Step 4).
Figure 2.3.2.2.2-5: BST Manager
– DHW & Other: DHW Analog Input Screen
B. If you chose
Network
or
BAS
, the
Other Operating Mode
screen appears (see
Step 4).
4. When all DHW parameters have been configured, the
Other Operating Mode
screen
appears. Choose either
Constant Setpoint
or
Remote Setpoint
. Press
Next
to continue.
Figure 2.3.2.2.2-6: BST Manager
– DHW & Other: Other Operating Mode Screen
5. If you chose
Constant Setpoint
, specify the setpoint for the
“other” application. Pressing
Next
takes you to the
Select BAS Mode
Figure 2.3.2.2.2-7: BST Manager
– DHW & Other: Other Heating Constant Setpoint