6.2.5 Freeze Protection
The
Freeze Protection
screen contains parameters that can prevent damage due to freeze
conditions.
1. Go to:
Main Menu
→
Advanced Setup
→
Unit
→
Freeze Protection
.
Figure 6.2.5: Unit: Freeze Protection Screen
– Shown Enabled
2. If desired, set
Freeze Protection
to
Enabled
.
3. Once
Enabled
,
the following additional parameters appear, which determine when the unit
will shut off and restart:
•
Pump On Temperature
:
Ambient t
emperature below this value
triggers system
pump to start
. (Range: 20 to 245°F)
•
Unit On Temperature
:
Ambient t
emperature below this value
triggers the unit to
fire.
(Range: 20 to 245°F)
•
Stop Temperature
:
Ambient
temperature above this value
returns system to
normal operation
.
(Range: 20 to 245°F)
6.2.6 Unit Application Configuration
The
unit’s
Application Configuration
screen contains operating mode, temperature and
setpoint parameters for Standalone units.
NOTES:
•
This option is
disabled (greyed out) if
Unit Mode
=
BST Client
or
BST Manager
in
, below (it appears only if
Unit Mode
=
Off
).
•
Some parameters below appear in EZ Setup (see Section 2). EZ Setup walks you through
a full configuration while this screen allows you modify individual parameters.
1. Go to:
Main Menu
→
Advanced Setup
→
Unit
→
Application Configuration
.