Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
118
of
196
NOTE:
Once BST Cascade functionality is enabled, you can navigate from one BST Cascade screen
to the next in round-robin fashion using the Page Left and Page Right icons.
6.3.1 Cascade Configuration
Boiler Sequencing Technology (BST) functionality is enabled from this screen by setting
Unit
Mode
to either
BST
Manager
or
BST
Client
(default =
Off
).
Once either
BST
Manager
or
BST
Client
is enabled, the following occurs:
•
If the unit is configured as a
BST Manager
, all parameters below (and all other BST
Cascade sections) apply to all units in the BST cascade, and will take precedence over
the same parameters on units configured as a
BST Client
.
•
The unit
Application Configuration
screen for standalone units (in
Unit
Application Configuration
) is disabled.
•
Additional BST parameters appear on the screen. The specific parameters depend on
whether
BST
Manager
or
BST
Client
was selected, and on
the current value of various
parameter in
the available parameters are
shown in the table in Step 3, below
:
1. Go to:
Main Menu
→
Advanced Setup
→
BST Cascade
→
Cascade Configuration
.
Figure 6.3.1-1: BST Cascade: Cascade Configuration Screen
2. To designate the current unit as a BST Client or BST Manager, press
Unit Mode
and
choose
BST
Client
or
BST
Manager
.