Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
127
of
196
TABLE 6.10: Application = Other+DHW-Stpt Prty
Other DHW PRI Setpt Mode
Other DHW PRI Setpoint (if Other DHW PRI Setpt Mode = Constant Setpoint)
Other DHW PRI Remote Signl (if Other SDHW PRI Setpt Mode = Remote Setpoint)
In the table below, the prerequisite for a parameter to appear on the screen is shown in
parentheses.
NOTE
: Applications are numbered from 1 to 8, per Table 6.4, above.
TABLE 6.11: Parameter Descriptions
Item Name
Description
1
Application
Choose
SH
(1) through
Other+DHW-Stpt Prty
(8)
2
SH Operating Mode
(
Application
=
1
,
4
-
7
) Choose:
Constant Setpoint,
Remote
Setpoint
or
Outdoor Air Reset
3
Other Operating Mode
(
Application
=
3
,
7
or
8
) Choose either
Constant Setpoint
or
Remote Setpoint
4
DHW Operating Mode
(
Application
=
2
,
4
-
6
,
8
) Choose either
Constant Setpoint
or
Remote Setpoint
5
SH Setpoint
(
Application
=
1
,
4
-
8
;
SH Operating Mode
=
Constant
Setpoint
) Specify the Space Heating setpoint for the plant.
(Range: 60°F to 245°F)
6
DHW Setpoint
(
Application
=
2
,
4
-
6
,
8
;
DHW Operating Mode
=
Constant
Setpoint
) Specify the setpoint for DHW application.
(Range: 60°F to 245°F)
7
Other Rmt Setpt Signal
(
Application
=
2
,
7
,
8
;
Other Operating Mode =
Remote
Setpoint
) Choose the remote signal type
for the “other”
Application:
1-5V
,
0-5V
or
Network
.
8
Other Rmt Setpt Source
(
Application
=
2
,
7
,
8
;
Other Rmt Setpt Signal =
1-5V
or
0-5V
)
Choose the remote setpoint source:
Spare Analog In 1
,
Spare
Analog In 2
or
Spare Analog In 3
.
9
SH Rmt Setpt Source
(
Application
=
1
,
4
–
7
;
SH Operating Mode
=
Remote
Setpoint
) Choose the remote signal type:
4-20mA
,
20mA
,
1-5V
,
0-5V
,
Network
or
BAS
.
10
DHW Rem Setpt Signal
(
Application
=
2
,
4
-
6
,
8
;
DHW Operating Mode
=
Remote
Setpoint
) Choose the remote signal type:
1-5V
,
0-5V
,
Network
or
BAS
.
11
BST Outdoor Temp
(
Application
=
1
,
3
–
7
,
SH Operating Mode
=
Outdoor Air
Reset
,
Outdoor Air Temp Sens
≠
OFF
in
Cascade Configuration
screen) A read-only display indicating how the unit
communicates with the Outdoor Air Temp Sensor
12
Outdoor Rst Setpt
(
Application
=
1
,
4
,
5
,
7
;
SH Operating Mode
=
Outdoor Air
Reset
,
Outdoor Air Temp Sens
≠
OFF
in
Cascade Configuration
screen) A read-only display indicating the current outdoor reset
setpoint based on the four OAR parameters (items 15-18).