Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
32
of
196
5. The next screen displays the current time and date. If both are correct, press
Next
to
continue. If not, press either field and enter the correct time or date and then press
Save
.
Figure 2.3.2-7: BST Manager: Date and Time Screen
6. Fill in the settings on the
Cascade Communication
screen, described below. When done,
press
Next
to continue.
Figure 2.3.2-4: BST Manager: Manager Communication Screen
NOTE:
Many of these parameters also appear in
Section 6.3.2: Cascade Communication
, where
individual settings can be easily changed at a later time.
•
Unit Address
: The unique communication address of the current (Manager) unit.
(Range: 1 to 127)
•
Min & Max Address
: The address range in the BST cascade,
1
up to the total
number of units in the cascade; for example,
1
and
10
(
Max Address
maximum =
16
).
•
SSD Address
: The Client/Client Device address. This parameter is for backwards
compatibility with the C-More Control system.
•
Cascade Baud Rate
: Select the rate at which information is transferred in a
communication channel:
9600
,
19200
,
38400
,
115200
bits per second.
•
Plant Failsafe Mode
: The
Manager’s operating mode if there is a loss of
communication between the Manager and Client units, or to the BAS or external
signal/sensor, such as an outdoor sensor (default =
Constant Setpoint
).
•
Plant Failsafe Setpoint
: (only if
Plant Failsafe Mode
=
Constant Setpoint)
Specify the
Setpoint for all units in the cascade.