Edge [ii] Controller Operation Manual
SECTION 7
– UNIT STATUS
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
174
of
196
7.3 Plant Status
The Plant Status screen is displayed in the round-robin on BST Manager units only.
Figure 7.3: Plant Status Screen
The following notes apply to this screen:
•
The
Outside Temp
(Outdoor Air Temp Sensor),
Sys Return
(Rtn Hdr Temp Sensor),
SH Supply
(Hdr Temp Sensor),
DHW Supply
(DHW Temp Sensor) and
Other
Supply
(Loop 2 Supply, not shown) are displayed when the associated sensors are
enabled as part of a BST Cascade. If a given sensor is enabled but no sensor is
detected, the screen displays
“
Open
”
for the missing data.
•
A maximum of two Setpoint and Supply data can be displayed, based on the Application
chosen in
Space Heating
and
DHW
,
Space Heating
and
Other
or
DHW
and
Other
can be active simultaneously). If only
one application is active, one Setpoint and Supply data are displayed.
•
The screen displays
Sys Fire Rate
unless the Plant is configured for
DHW Swing
Boiler
configuration.
•
If the Plant is configured for
DHW Swing Boiler
configuration, the screen displays
DHW Fire Rate
.