Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
120
of
196
6b VSP Pump Off Delay (Item 6
≠ Off)
✓
✓
✓
✓
✓
✓
6c VSP Pump Output (Item 6
≠ Off)
✓
✓
✓
✓
✓
✓
6d VSP Pump Relay (Item 6
≠ Off)
✓
✓
✓
✓
✓
✓
6e VSP Piping Configuration (Item 6 = Fire Rate)
✓
✓
✓
✓
✓
✓
6f Boiler Plant Size (Item 6 = Fire Rate)
✓
✓
✓
✓
✓
✓
6g Plant VSP Pump min spd (Item 6 = Fire Rate)
✓
✓
✓
✓
✓
✓
6h Plant VSP Pump max spd (Item 6 = Fire Rate)
✓
✓
✓
✓
✓
✓
6i Rem Blr VS Pump Add (Item 6 = Fire Rate)
✓
✓
✓
✓
✓
✓
6j VSP Pump Decrease (Item 6 = Return Temp)
✓
✓
✓
✓
✓
✓
6k VSP Pump Decr Time (Item 6 = Return Temp
✓
✓
✓
✓
✓
✓
6l VSP Pump Incr Time (Item 6 = Return Temp
✓
✓
✓
✓
✓
✓
6m VSP Pump Off Delay (Item 6 = Return Temp
✓
✓
✓
✓
✓
✓
•
Item 1:
Auto-Manager Transfer
: If enabled, BST Manager functionality can be
transferred to a designated Backup Manager. The Backup Manager must be
connected to all system level sensors, either via dual lead sensors or via Modbus
wiring. When enabled, the following additional parameters appear:
o
Item 1a:
Auto-Manager Timer
:
Specifies the time before switching over
Manager functionality. (Range: 10 to 120 seconds, Default = 30)
o
Item 1b:
Auto-Manager Addr
: A read-only display of the
address of the current
BST Manager.
o
Item 1c:
Backup Manager Addr
: Enter the address of the unit designated as
the Backup Manager. It can be any address above
0
except the value of
Auto-
Manager Addr
. (Range: 0 to 16)
•
Item 2:
Hdr Temp Sensor
:
If plant operation is based on feedback from the
Header Temp Sensor, choose how to communicate with the sensor:
o
Network
: Choose this option if the Header Temp Sensor is wired to the Modbus
transmitter. If chosen, the following additional parameter appears:
▪
Item 2a:
SH Hdr Temp Point
: The Modbus point within the Modbus
address of the Header Temp Sensor (Range: 0 to 255, default = 14).
▪
Item 2b:
SH Sensor Comm Addr
: Specifies the Modbus transmitter
address (common to all Modbus sensors). (Range: 0 to 255, default = 240)
o
FFWD Temp
: Choose this option only if
Control Type
=
C-More
(in
); FFWD is the direct connect option in the C-More.
o
Direct
: Choose this option if the Modbus transmitter is connected directly to the
unit.
o
BAS
: Choose this option if header temperature is received from the
site’s Building
Automation System.
o
OFF
: Disables header temperature sensor feedback functionality.
•
Item 3:
DHW Temp Sensor
: Choose how to communicate with the sensor:
o
Off
: Disables DHW temperature sensor functionality.
o
Network
: Choose this option if DHW temp sensor is wired to the Modbus
transmitter. If chosen, the following additional parameter appears:
▪
Item 3a:
DHW Hdr Sens Point
: Specify the Modbus point within the
Modbus address where the DHW temp sensor resides.
(Range: 0 to 255, default = 17)