Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
38
of
196
1. The
DHW Operating Mode
screen appears. Choose the
Operating Mode
for the DHW
application, either
Constant Setpoint
or
Remote Setpoint
, then press
Next
to continue.
Figure 2.3.2.1.2-2: BST Manager
– DHW: DHW Operating Mode Screen
2. If you chose
Constant Setpoint
, specify the
DHW Constant Setpoint
. Pressing
Next
takes you to the
Select BAS Mode
screen; skip to
for instructions.
Figure 2.3.2.1.2-3: BST Manager
– DHW Constant Setpoint Screen
3. If you chose
Remote Setpoint
in step 1, the
Select Remote Setpoint Type
screen
appears. Choose how the unit will access the setpoint, then press
Next
.
Figure 2.3.2.1.2-4: BST Manager
– DHW: Select Remote Setpoint Screen
A. If you chose
4-20mA
,
or
0-20mA
,
the
DHW Analog Input
screen appears. Fill in the
parameters listed below:
•
Press
DHW Rmt Setpt Source
and choose the source of the remote
setpoint (the previous choice, if there was one, has a green border):
Spare
Analog in 1
,
Spare Analog in 2
or
Spare Analog in 3
.