4.5 System
From the
System
screen you can run a programmable profile, manually ramp the fire rate up or
down, perform a pre-startup diagnostic or view a software version summary.
1. Go to:
Main Menu
→
Diagnostics
→
System
.
Figure 4.5: Diagnostics: System Screen
NOTE:
You can navigate from the
Pre-Start Up
screen to
Versions
in round-robin fashion
using the
Page Left
and
Page Right
icons on each screen.
4.5.1 Pre-Start Up
The
Pre-Start Up
screen allows you verify various system components and assemblies without
opening the SSOV. This is particularly useful when the building
’s gas supply has not been
turned on and you want to make sure everything will function when the gas supply is turned on.
Complete the instructions below to run Pre-Start Up diagnostic tests.
2. Go to:
Main Menu
→
Diagnostics
→
System
→
Pre-Start Up
.
Figure 4.5.1: System: Pre-Start Up Screen
– Shown Disabled
3. To run the Pre-Startup test, enable the
Pre-Start Up Mode
control. The following occurs:
•
The valve position moves to ignition position.
•
The Blower is turned on at ignition point voltage.