Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
95
of
196
6.2.1 Unit Settings
The
Unit Settings
screens displays a list of parameters and controls on several pages. Many of
the parameters were set at the factory before shipping and should not be changed.
1. Go to:
Main Menu
→
Advanced Setup
→
Unit
→
Unit Settings
.
Figure 6.2.1-1: Unit: Unit Settings Screens
2. The following fields are available:
•
Unit Serial #
:
Displays the unit’s factory-set serial number in a unique format of G-
YY-ZZZZ or N-YY-ZZZZ. Do
NOT
change except if replacing the Edge Controller. The
format is:
o
G
: A letter specific to Benchmark 750-4000 boilers and Innovation Water
Heaters. The letter
N
is specific to Benchmark 5000 & 6000 boilers.
o
YY
: The two-digit year
o
ZZZZ: A sequential 4-digit serial number.
•
Unit Type
: Displays AERCO products and models. Do
NOT
change except if
replacing the Edge Controller.
•
KC Boiler
•
BMK Boiler Std
•
BMK Boiler LN
•
KC Boiler LN
•
BMK Boiler Std Dual
•
BMK Boiler LN Dual
•
Unit Size
: Displays available sizes for the given
Unit Type
. Do
NOT
change unless
replacing the Edge Controller.
•
Control Type
: Specifies the controller:
Edge
[ii] (the default for all Platinum units) or
Edge [i]
. Do
NOT
change unless replacing the Edge Controller with an Edge [i]
Controller.