VD500 Series Inverter User Manual Function Parameter Table
- 71 -
Fb-14
Hopping
Frequency Range
0.01Hz~max frequency
0.01Hz
○
Fb-15
Hopping
Frequency
Whether Valid in
the Process of
Acceleration/decel
eration
0: Disabled
1: Enabled
0
○
Fb-16
Frequency
Detection Value
(FDT1)
0.00Hz~max frequency
50.00Hz
○
Fb-17
Frequency
Detection Lagged
Value (FDTI)
0.0%~100.0% (FDT1 electrical level )
5.0%
○
Fb-18
Frequency
Detection Value
(FDT2)
0.00Hz~max frequency
50.00Hz
○
Fb-19
Frequency
Detection Lagged
Value (FDT2)
0.0%~100.0% (FDT2 electrical level )
5.0%
○
Fb-20
Frequency
Reached
Detection
Amplitude
0.0%~100.0% (max frequency)
0.0%
○
Fb-21
Any Frequency
Reaching
Detection Value 1
0.00Hz~max frequency
50.00Hz
○
Fb-22
Any Frequency
Reaching
Detection
Amplitude 1
0.0%~100.0% (max frequency)
0.0%
○
Fb-23
Any Frequency
Reaching
Detection Value 2
0.00Hz~max frequency
50.00Hz
○
Fb-24
Any Frequency
Reaching
Detection
Amplitude 2
0.0%~100.0% (max frequency)
0.0%
○
Fb-25
Zero Current
Detection Levels
0.0%~300.0%
100.0% corresponding rated motor
current
5.0%
○
Fb-26
Zero Current
Detection Delay
Time
0.01s~600.00s
0.1s
○
Fb-27
Output Current
Limit Exceed
0.0% (no detection)
0.1%~300.0% (rated motor current)
200.0%
○