Function Parameter Table VD500 Series Inverter User Manual
- 66 -
1: Stop according to stop mode
2: Continue to run
Ten’s digit: input phase loss (13)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Hundred’s digit: output phase loss
(14)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Thousand’s digit: external fault (17)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten thousand’s digit: communication
abnormal (18)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
F9-37
Fault Protection
Action Selection 2
Unit’s digit: encoder / PG card
abnormal (31)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten’s digit: parameter read-write
abnormal (21)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Hundred’s digit: running time reached
(27)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Thousand’s digit: speed deviation is
too larg (40)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten thousand’s digit: motor overspeed
(41)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
0x00000
○
Содержание VD500 Series
Страница 2: ......
Страница 9: ...VD500 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce...