Parameter Description VD500 Series Inverter User Manual
- 174 -
2: AI2
3: AI3 (expansion card)
4: PULSE
5: Communication setting
6: Keypad potentiometer
A0-06
Max Frequency Digital
Setting under the Torque
Control Reverse
0.00Hz~max frequency
50.00
Hz
○
Used to set the forward or reverse maximum running frequency of the inverter under the torque
control mode.
When the inverter torque control, if the load torque is less than the motor output torque, the motor
speed will continue to rise, to prevent mechanical systems appear coasters and other accidents, must
limit the motor highest speed when torque control.
A0-07
Torque Control
Acceleration Time
0.00s~650.00s
0.00s
○
A0-08
Torque Control
deceleration Time
0.00s~650.00s
0.00s
○
Under the torque control mode, the difference between the motor output torque and load torque,
determine the speed change rate of the motor and load, so the speed of the motor can be changed
quickly, which brings the problems such as high noise or mechanical stress. By setting the torque
control acceleration and deceleration time, the motor speed can change smoothly.
But for the occasion need torque rapid response, you need to set the torque control acceleration and
deceleration time is 0.00 s.
For example: two motor hard-wired drag the same load, in order to ensure the load uniform
distribution, set a frequency inverter for the host, using the speed control mode, another inverter for
the host and using torque control, the actual output torque of the host as the torque instructions of
slave, the slave torque needs to quickly follow the host at this point, so the torque control acceleration
and deceleration time of slave is 0.00s.
A0-09
Starting Torque Setting
0.0%~100.0%
10.0%
○
A0-10
Excitation Current
Coefficient under the
Torque Control (only
effective to SVC)
20.0%~150.0%
100.0%
○
Torque control parameters, according to the actual situation to set the appropriate value.
A0-11
Low Frequency Torque
Compensation Amount
0.0%~50.0%
0.0%
○
A0-12
Low Frequency Torque
Compensation
Frequency Upper Limit
0.00Hz~Max frequency
10.00Hz
○
A0-13
High Frequency Torque
Compensation Amount
0.0%~50.0%
3.0%
○
A0-14
High Frequency Torque
Compensation
Frequency Upper Limit
0.00Hz~Max frequency
25.00Hz
○
The related parameters of the torque compensation, torque compensation for low frequency and high
frequency, stable output.
Содержание VD500 Series
Страница 2: ......
Страница 9: ...VD500 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce...