b2 AI Curve Setting Parameter Group
b2-00
AI Curve 4 Min Input
-10.00V~b2-02
0.00V
○
b2-01
Corresponding Setting of
AI Curve 4 Min Input
-100.0%~+100.0%
0.0%
○
b2-02
AI Curve 4 Inflection
Point 1 Input
b2-00~b2-04
3.00V
○
b2-03
Corresponding Setting of
AI Curve 4 Inflection
Point 1 Input
-100.0%~+100.0%
30.0%
○
b2-04
AI Curve 4 Inflection
Point 2 Input
b2-00~b2-06
6.00V
○
b2-05
Corresponding Setting of
AI Curve 4 Inflection
Point 2 Input
-100.0%~+100.0%
60.0%
○
b2-06
AI Curve 4 Max Input
b2-06~+10.00V
10.00V
○
b2-07
Corresponding Setting of
AI Curve 4 Max Input
-100.0%~+100.0%
100.0%
○
b2-08
AI Curve 5 Min Input
-10.00V~b2-10
-10.00V
○
b2-09
Corresponding Setting of
AI Curve 5 Min Input
-100.0%~+100.0%
-100.0%
○
b2-10
AI Curve 5 Inflection
Point 1 Input
b2-08~b2-12
-3.00V
○
b2-11
Corresponding Setting of
AI Curve 5 Inflection
Point 1 Input
-100.0%~+100.0%
-30.0%
○
b2-12
AI Curve 5 Inflection
Point 2 Input
b2-10~b2-14
3.00V
○
b2-13
Corresponding Setting of
AI Curve 5 Inflection
Point 2 Input
-100.0%~+100.0%
30.0%
○
b2-14
AI Curve 5 Max Input
b2-12~+10.00V
10.00V
○
b2-15
Corresponding Setting of
AI Curve 5 Max Input
-100.0%~+100.0%
100.0%
○
The function of curve 4 and 5 are similar with curve 1~3, but the curve 1~3 is a straight line, while the
curve 4 and 5 is 4 point curve, can realize more flexible corresponding relation. The diagram below is
curve 4~5.