VD500 Series Inverter User Manual Function Parameter Table
- 61 -
Places
2: 2 bit decimal place
3: 3 bit decimal place
F8 Protection Parameters
Function
Code
Parameter Name
Setting Range
Factory
Default
Value
Property
F8-00
Motor 1 Overload
Protection
Selection
0: Disabled
1 : Enabled
1
○
F8-01
Motor 1 Overload
Protection Gain
0.20~10.00
1.00
○
F8-02
Motor 1 Overload
Warning
Coefficient
50%~100%
80%
○
F8-03
Motor 2 Overload
Protection
Selection
0: Disabled
1: Enabled
0
○
F8-04
Motor 1 Overload
Protection Gain
0.20~10.00
1.00
○
F8-05
Motor 1 Overload
Pre-alarm
Coefficient
50%~100%
80%
○
≤11kW: 1
F8-06
Overvoltage / over
current Stall Mode
Selection
0: Mode 0
1: Mode 1
>11kW: 0
◎
F8-07
Overvoltage Stall
Proportion Gain
0: Disabled
1~100
10
○
F8-08
Overvoltage Stall
Integral Gain
0~100
10
○
380VAC: 700.0VDC
F8-09
Overvoltage Stall
Protection voltage
100.0VDC~800.0VDC
220VAC: 370.0VDC
○
F8-10
Over current Stall
Proportion Gain
0: Disabled
1~1000
20
○
F8-11
Over current Stall
Integral Gain
0~1000
20
○
F8-12
Over current Stall
Protection Current
100%~200%
160%
○
F8-13
Quick Start Over
current
Suppression Gain
0~1000
30
○
F8-14
Short-circuit to
Ground Upon
Power-on
0: Invalid
1: Valid
1
○