Parameter Description VD500 Series Inverter User Manual
- 156 -
acceleration and deceleration.
Hopping frequency range
Hopping
frequency 2
Hopping
frequency 2
Time(t)
Output
frequency(Hz)
Hopping frequency range
Hopping frequency range
Hopping frequency range
Fig 6-22 Effective schematic diagram of hopping frequency in the process of acceleration and deceleration
Fb-16
Frequency Detection
Value (FDT1)
0.00Hz~max frequency
50.00Hz
○
Fb-17
Frequency Detection
Lagged Value (FDTI)
0.0%~100.0% (FDT1 electrical level )
5.0%
○
Fb-18
Frequency Detection
Value (FDT2)
0.00Hz~max frequency
50.00Hz
○
Fb-19
Frequency Detection
Lagged Value (FDT2)
0.0%~100.0% (FDT2 electrical level )
5.0%
○
When the running frequency is higher than the frequency detecion values, the frequency converter
multi-function output DO output ON signal, and the frequency is lower than a certain frequency values
of the detection values, the DO output ON signal is cancelled.
The above parameters are used to set the detection value of output frequency, and cancel the lag
value of the output motion. Among them, the Fb-17 (Fb-19) is the percentage of lagging frequency
relative to the frequency detection values Fb- 6 (Fb-18). The diagram below for the FDT function.
FDT Lagged
value=Fb-
16*Fb-17 or
Fb-18*Fb-19
Time(t)
Output
frequency(Hz)
FDT Electrical
level
Frequency
reaching
detection signal
(
DO relay
)
ON
Time(t)
Fig 6-23 Schematic diagram of FDT electrical level