Function Parameter Table VD500 Series Inverter User Manual
- 56 -
F6-00
HDO1 Terminals
Output Mode
Selection
0: HS Pulse output
1: Switch signal output
0
○
F6-01
HDO1 Terminals
Output Function
Mode Selection
0
○
F6-02
Relay T1 Function
Selection
0
○
F6-03
Relay T2 Function
Selection
0
○
F6-04
DO1 Output
Terminal Function
Selection
0: No output
1: Inverter in running
2: Ready for run
3: Fault output 1 (fault stop)
4: Fault output 2 (don’t output
undervoltage)
5: Warning output (continue to run)
6: Output undervoltage
7: Frequency level detection FDT1
output
8: Frequency level detection FDT2
output
9: Frequency reached
10: Frequency 1 reached output
11: Frequency 2 reached output
12: Zero speed running 1 (no output
when stop)
13: Zero speed running 2 (output
when stop)
14: Frequency upper limit reached
15: Frequency lower limit reached
(about running)
16: Frequency lower limit reached
(output when stop)
17: Current 1 reached output
18: Current 2 reached output
19: Zero current state
20: Output current limit exceeded
21: Motor overload pre-alarm
22: Inverter overload pre-alarm
23: During the load
24: Set Count value reached
25: Designated count value reached
26: Length reached
27: Module temperature reached
28: Reserved
29: Current running time reached
30: Accumulative running time
reached
31: Accumulative power-on time
reached
32: Timing reached output
33: PLC circulation output
0
○