VD500 Series Inverter User Manual Function Parameter Table
- 45 -
Thousand’s digit: Automatic operation
command binding frequency source
selection, same as above
F0-23
Communication
Protocol Selection
0: Modbus
0
●
F0-24
Motor Selection
0: Motor 1
1: Motor 2
0
◎
F0-25
GP Type Selection
1: G type (constant torque load model)
2: P type (fan, pump type load models)
1
◎
F1 Start/Stop Control Group
Function
Code
Parameter Name
Setting Range
Factory
Default
Value
Property
F1-00
Start Mode
0: Direct start
1: Speed tracking restart
2: Pre excitation start (AC
asynchronous)
0
○
F1-01
Starting Frequency 0.00Hz~10.00Hz
0.50Hz
○
F1-02
Startup Frequency
Holding Time
0.00s~60.00s
0.0s
◎
F1-03
Starting DC
Braking Current/
Pre-excitation
Current
0%~100%
0%
◎
F1-04
Starting DC
Braking Current/
Pre-excitation
Current
0.0s~100.0s
0.0s
◎
F1-05
Speed Tracking
Mode
0: Starting from the stop frequency
1: Starting from zero speed
2: Starting from maximum frequency
0
◎
F1-06
Speed Tracking
Speed
1~100
20
○
F1-07
Speed Tracking
Current
100%~150%
125%
◎
F1-08
Stop Mode
0: Decelerate to stop
1: Coast to stop
0
○
F1-09
Initial Frequency of
Stop DC Braking
0.00Hz~max frequency
0.00Hz
○
F1-10
Waiting Time of
Stop DC Braking
0.0s~100.0s
0.0s
○