Parameter Description VD500 Series Inverter User Manual
- 148 -
2: Continue to run
Thousand’s digit: offload (37)
0: Coast to stop
1: Stop according to stop mode
2: Decelerate to 7% of the rated motor
frequency continue running,
automatically restored to the set
frequency operation when no offload
Ten thousand’s digit: PID feedback lost
when running (18)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
F9-39
Fault Protection Action
Selection 4
Unit’s digit: user-defined fault (22)
0: Coast to stop
1: Stop according to stop mode
2: Continue to run
Ten’s digit: reserved
Hundred’s digit: reserved
Thousand’s digit: reserved
Ten thousand’s digit: reserved
0x000
00
○
When the option is "coast to stop", inverter show Err. * *, and directly downtime.
When the option is "according to the stop way to stop”: inverter show A. * *, and press down way
down, show Err. * * after stop.
When the option is "continue to run" : frequency converter continue to run and displays A. * *, running
frequency is set by F9-40.
F9-40
Continue Running
Frequency Selection at
Failure
0: Run to the current running frequency
1: Run at set frequency
2: Run at frequency upper limit
3: Run at frequency lower limit
4: Run at abnormal standby frequency
0
○
F9-41
Abnormal Standby
Frequency
60.0%~100.0%
(100.0% corresponding max frequency
F0-10)
100.0%
○
When the inverter malfunction during the operation, and the processing mode of fault is set to
continue to run, frequency converter show A. **, and operation according to the frequency of F9-40
determine.
When operation selecting an anomaly standby frequency, the value set by F9-41 is the percentage
relative to the maximum frequency.
Содержание VD500 Series
Страница 2: ......
Страница 9: ...VD500 Series Inverter User Manual Safety and Precautions 5 damage or performance reduce...