Parameter Description VD500 Series Inverter User Manual
- 154 -
Fb Enhance Function Group
Fb-00
Jog Running Frequency
0.00Hz~max frequency
5.00Hz
○
Fb-01
Jog Acceleration Time
0.0s~6500.0s
Model dependent
○
Fb-02
Jog Deceleration Time
0.0s~6500.0s
Model dependent
○
Definition the given frequency and acceleration/deceleration time of frequency converter in jog.
When jog running, the start mode is fixed to the direct start mode (F1-00=0) and the stop mode is
fixed to the deceleration stop (F1-08=0).
Fb-03
Acceleration Time 2
0.0s~6500.0s
Model dependent
○
Fb-04
Deceleration Time 2
0.0s~6500.0s
Model dependent
○
Fb-05
Acceleration Time 3
0.0s~6500.0s
Model dependent
○
Fb-06
Deceleration Time 3
0.0s~6500.0s
Model dependent
○
Fb-07
Acceleration Time 4
0.0s~6500.0s
Model dependent
○
Fb-08
Deceleration Time 4
0.0s~6500.0s
Model dependent
○
VD500 provide four groups of acceleration/deceleration time, respectively F0-18/F0-19 and the above
three groups of acceleration/deceleration time.
The definition of four groups of acceleration/deceleration time are exactly the same, please reference
F0-18 and F0-19 related instructions.
Through the different combination of the multi-function digital inputs terminal DI, it can be switched to
select 4 groups of acceleration/deceleration time.
Schedule 1 is the terminal functional specifications of acceleration/deceleration time selection.
Terminal 2 Terminal 1
Acceleration/deceleration time selection
Corresponding Parameter
OFF
OFF
Acceleration time 1
F0-18, F0-19
OFF
ON
Acceleration time 2
Fb-03, Fb-04
ON
OFF
Acceleration time 3
Fb-05, Fb-06
ON
ON
Acceleration time 4
Fb-07, Fb-08
Fb-09
Emergency Stop Time
0.0s~6500.0s
10.s
○
When the DI function 30 is effective, the set time of Fb-09 will be delecerate to stop.
Fb-10
Acceleration Time 1 and
time 2 Switching
Frequency Point
0.00Hz~max frequency
0.00Hz
○
Fb-11
Deceleration Time 1 and
time 2 Switching
Frequency Point
0.00Hz~max frequency
0.00Hz
○
The function in the motor selection for 1 and not through the DI terminal switch to select the
acceleration/deceleration time effectively. Used in the process of inverter running, not through the DI
terminal but according to the running frequency range, selection different acceleration/deceleration
time.