VD500 Series Inverter User Manual Parameter Description
- 135 -
F6-07
HDO1 Closing Delay
0.0s~3600.0s
0.0s
○
F6-08
T1 Closing Delay
0.0s~3600.0s
0.0s
○
F6-09
T2 Closing Delay
0.0s~3600.0s
0.0s
○
F6-10
DO1 Closing Delay
0.0s~3600.0s
0.0s
○
F6-11
DO5 Closing Delay
0.0s~3600.0s
0.0s
○
Set the delay time of output terminal HDO1, relay 1, relay 2 and DO1 from state changes to the actual
output changes.
F6-12
HDO1 Output Function
Selection
0
○
F6-13
AO1 Output Function
Selection
0
○
F6-14
AO2 Output Function
Selection
0~15, see table below
1
○
Analog output AO1 and AO2 output range is 0V~10V or 0/4mA~20mA. HDO1 terminal output pulse
frequency range is 0.01kHz~F6-15(output max frequency when HDO1 pulse output mode), F6-15
can be set from 0.01kHz~100.00kHz. Pulse or analog signal output 0.0%~100.0% corresponding
function as below table:
Set
value
Function
Description
0
Running frequency
0~maximum output frequency
1
Set frequency
0~maximum output frequency
2
Output current
0~2 times of rated motor current
3
Output torque
0~2 times of rated motor voltage
4
Output power
0~2 times of rated power
5
Output voltage
0~1.2 times of inverter rated power
6
PULSE input (100%
corresponding
100.0kHz)
0.01kHz~100.00kHz
7
AI1
0V~10V
8
AI2
0V~10V (or 0~20mA)
9
AI3 (expansion card)
0V~10V (or 0~20mA)
10
Length
0~maximum set length
11
Count value
0~Max count value
12
Communication
setting
0.0%~100.0%
13
Motor rotate speed
0~maximum output frequency corresponding rotate speed
14
Output current
When≤55Kw, 100% corresponding 100.00A; when >55kW,
100% corresponding 1000.0A