TB1 120VAC TERMINAL LAYOUT
1
2
3
4
5
6
7
8
9
10
H
N
H
N
FAN POWER 120VAC OUT
H
N
TB2 24V TERMINAL LAYOUT
19
20
21
22
23
24
25
26
27
28
29
30
FC AUX RELAY #3 AND BYPASS TIMER (24VDC FC POWER SOURCE)
FC 24VDC COMMON
HVAC SHUTDOWN
RACK#1 UPS SHUTDOWN*
RACK#3 UPS SHUTDOWN*
RACK#4 UPS SHUTDOWN*
RACK#5 UPS SHUTDOWN*
RACK#6 UPS SHUTDOWN*
125
124
123
122
121
120
119
117
118
116
115
114
112
113
111
110
109
108
107
106
103
105
104
102
101
150
149
148
147
146
145
144
142
143
141
140
139
137
138
136
135
134
133
132
131
128
130
129
127
126
CENTRAL OR RACK#1 UPS SHUTDOWN N.O. JUMPER
31
32
33
34
35
36
37
38
REDUNDANT HVAC SHUTDOWN*
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
FIRE CONTROLLER AUX RELAY#2 (NOT USED IN 500B AND 500BMB UNITS)
HVAC FAULT INPUT
PLENUM THERMOSTAT
REDUNDANT HVAC FAULT INPUT*
REDUNDANT PLENUM THERMOSTAT*
LOCAL EPO CONTACT #1 (PUSHBUTTON)
REMOTE EPO CONTACT #1* (REMOVE JUMPER IF USED)
LOCAL EPO CONTACT #2 (PUSHBUTTON)
REMOTE EPO CONTACT #2* (REMOVE JUMPER IF USED)
TB2 24V TERMINAL LAYOUT (CONTINUED)
SMOKE DETECTOR - TOP PLENUM
3
4
5
9
10
14
TO P3-2 FC
4.3K
EOL
TO P3-1 FC
TO P4-3 FC
TO P4-2 FC
39
40
HIGH TEMPERATURE FAULT
120VAC MAIN BREAKER SHUNT TRIP (IF SUPPLIED)
H
N
REMOVE IF NOT USING SOURCE B (N.O. CONTACT ONLY)
26A
COM
N.C.
N.O.
CONTROL POWER INPUT FROM SOURCE "A" 120VAC
CONTROL POWER INPUT FROM SOURCE "B" 120VAC*
FROM PANELBOARD CB1(UPS SUPPLIED)
FROM SECONDARY PANELBOARD CB1(UPS SUPPLIED)
28A
28B
28C
RACK#2 UPS SHUTDOWN*
COM
N.C.
N.O.
RACK#2 UPS SHUTDOWN N.O. JUMPER
REMOVE IF NOT USING SOURCE B (N.O. CONTACT ONLY)
NOTES:
ORN DENOTES ORANGE WIRE
BLU DENOTES BLUE WIRE
1.
1.
3.
3.
4.
5.
2.
6.
8.
8.
9.
7.
TB1 TERMINAL BLOCK
BLK DENOTES BLACK WIRE
RED DENOTES RED WIRE
TB2 TERMINAL BLOCK
ALL WIRE 16AWG UNLESS NOTED
BLU/WHT DENOTES BLUE WIRE WITH WHITE TRACER
ORN/WHT DENOTES ORANGE WIRE WITH WHITE TRACER
10.
12.
* - DENOTES USER ON-SITE SUPPLIED WIRING
11.
SMOKE DETECTOR TERMINAL BLOCK
13.
FC = FIRE CONTROL PANEL
SMART ROW DCR
CONTROL PANEL & FIRE
SUPPRESSION POWER
CONNECTIONS
Содержание SmartRow DCR
Страница 1: ...SmartRow DCR 3 to 6 Rack 20 kW N N 1 and 5 to 10 Rack 36 kW N Cooling Units 60 Hz Installer User Guide...
Страница 6: ...Vertiv SmartRow DCR Installer User Guide 6...
Страница 12: ...Vertiv SmartRow DCR Installer User Guide 12 This page intentionally left blank...
Страница 52: ...Vertiv SmartRow DCR Installer User Guide 52 This page intentionally left blank...
Страница 66: ...Vertiv SmartRow DCR Installer User Guide 66 This page intentionally left blank...
Страница 70: ...Vertiv SmartRow DCR Installer User Guide 70 This page intentionally left blank...
Страница 72: ...Vertiv SmartRow DCR Installer User Guide 72 This page intentionally left blank...
Страница 76: ...Vertiv SmartRow DCR Installer User Guide 76 This page intentionally left blank...
Страница 82: ...Vertiv SmartRow DCR Installer User Guide 82 This page intentionally left blank...
Страница 101: ......