6.3 Additional Settings for 20-kW, 3- to 6-rack Systems—N Cooling
(1 PDX/PCW - one cooling unit on)
Before making these changes, complete the adjustments in
Liebert iCOM Setup for all SmartRow DCR
Make these settings in the iCOM Service menu:
•
System / Network Setup > S803 Teamwork Mode: 0 - No
•
Standby Settings / Lead-Lag > S515 Cascade: No
•
Standby Settings / Lead-Lag > S503 Rotation Frequency: No
6.4 Additional Settings for 20-kW, 3- to 6-rack Systems—N+1 cooling Only
(2 PDX/PCWs - one cooling unit on, one in standby)
These settings apply to a SmartRow DCR that has two Liebert PDX/PCWs, one operating and one in
standby mode.
Before making these changes, complete the adjustments in
Liebert iCOM Setup for all SmartRow DCR
These settings allow the cooling units to share the remote 2T temperature sensor data when the cooling
units are operating or on standby. This ensures that the temperature readings from all racks are factored
into the cooling capacity calculation (CFC: Call for Cooling). Additionally, if the heat load temporarily
exceeds the capacity of the SmartRow DCR’s operating cooling unit, the standby unit will be
automatically started to assist. When one cooling unit can again maintain the load the second unit will
return to standby mode (cooling and fans Off).
1. Make these settings in the iCOM Service Menu > System / Network Setup:
•
S803 Teamwork Mode: 1
•
S804 Teamwork is based on: Maximum
NOTE: The controlling temperature sensor (S102) must be properly selected (see
on page 55) before setting the Teamwork Mode, followed by setting
Standby and Cascade modes.
2. Make these settings in the iCOM Service Menu > Standby Settings / Lead-Lag:
•
S502 Number of Standby Units: 1
•
S503 Rotation Frequency: Every WED (schedule for convenient day)
•
S504 Rotate at: 09:00 (schedule at convenient time)
•
S505 Rotate by: 1
NOTE: We recommend scheduling the cooling system rotation to occur at a time the person in charge
of the SmartRow DCR operation is present.
•
S515 Cascade Units: Cooling
•
S516 Cascaded Units Delay: 3 min
•
S517 Cascaded Units Quick Start: 0 min
•
S518 Cascaded Units Control Delay: [blank]
•
S520 Cascaded Units Min Run: 5 minutes
Vertiv
| SmartRow DCR Installer/User Guide |
58
Содержание SmartRow DCR
Страница 1: ...SmartRow DCR 3 to 6 Rack 20 kW N N 1 and 5 to 10 Rack 36 kW N Cooling Units 60 Hz Installer User Guide...
Страница 6: ...Vertiv SmartRow DCR Installer User Guide 6...
Страница 12: ...Vertiv SmartRow DCR Installer User Guide 12 This page intentionally left blank...
Страница 52: ...Vertiv SmartRow DCR Installer User Guide 52 This page intentionally left blank...
Страница 66: ...Vertiv SmartRow DCR Installer User Guide 66 This page intentionally left blank...
Страница 70: ...Vertiv SmartRow DCR Installer User Guide 70 This page intentionally left blank...
Страница 72: ...Vertiv SmartRow DCR Installer User Guide 72 This page intentionally left blank...
Страница 76: ...Vertiv SmartRow DCR Installer User Guide 76 This page intentionally left blank...
Страница 82: ...Vertiv SmartRow DCR Installer User Guide 82 This page intentionally left blank...
Страница 101: ......