To enable this function:
1. Enter these changes in the iCOM Service Menu > System / Network Setup:
•
S803 Teamwork Mode:1
•
S804 Teamwork is based on: Maximum
NOTE: The controlling temperature sensor (S102) must be properly selected (see
on page 55) prior to setting the Teamwork Mode, followed by setting
Standby and Cascade modes.
2. Enter these changes in the iCOM Service Menu > Standby Settings / Lead-Lag:
•
S502 Number of Standby Units: 0 (the fans in both Liebert PDX/PCWs are always
running)
•
S503 Rotation Frequency: Every WED (schedule at a convenient time; see the Note that
follows)
•
S504 Rotate at: 09:00 (schedule at a convenient time; the Note that follows)
•
S505 Rotate by: 1
•
S515 Cascade Units: No (Teamwork Mode 1 will allow the cooling capacity to Cascade
while keeping the fans On constantly. Enabling Cascade would force the fans to turn Off,
which would prevent even distribution of cooling air.)
NOTE: We recommend scheduling the cooling system rotation to occur at a time the person in charge
of the SmartRow DCR operation is present.
Vertiv
| SmartRow DCR Installer/User Guide |
60
Содержание SmartRow DCR
Страница 1: ...SmartRow DCR 3 to 6 Rack 20 kW N N 1 and 5 to 10 Rack 36 kW N Cooling Units 60 Hz Installer User Guide...
Страница 6: ...Vertiv SmartRow DCR Installer User Guide 6...
Страница 12: ...Vertiv SmartRow DCR Installer User Guide 12 This page intentionally left blank...
Страница 52: ...Vertiv SmartRow DCR Installer User Guide 52 This page intentionally left blank...
Страница 66: ...Vertiv SmartRow DCR Installer User Guide 66 This page intentionally left blank...
Страница 70: ...Vertiv SmartRow DCR Installer User Guide 70 This page intentionally left blank...
Страница 72: ...Vertiv SmartRow DCR Installer User Guide 72 This page intentionally left blank...
Страница 76: ...Vertiv SmartRow DCR Installer User Guide 76 This page intentionally left blank...
Страница 82: ...Vertiv SmartRow DCR Installer User Guide 82 This page intentionally left blank...
Страница 101: ......