FORM NO. DPN001231 REV 4
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMBUS, OHIO 43229
REV#:
DRAWN BY:
CHECKED BY:
DATE:
ECN NUMBER:
SHEET NUMBER:
REFERENCE DRAWING:
QUOTE NUMBER:
DRAWING NUMBER:
1
BLR
04/17/17
TITLE / DESCRIPTION
CUSTOMER / JOB
CONTROL PANEL & FIRE SUPPRESSION
POWER DISTRIBUTION
SMARTROW DCR
SK
11
9
7
17
15
13
21
19
18
22
12
14
16
10
8
20A/1P
20
RACK #1 POWER
L1
N
208/120VAC
20A/1P
L2
L3
3 PHASE
RACK #2 POWER
L1
N
208/120VAC
L2
L3
3 PHASE
20A/1P
RACK #3 POWER
L1
N
208/120VAC
20A/1P
L2
L3
3 PHASE
RACK #4 POWER
L1
N
208/120VAC
L2
L3
3 PHASE
20A/1P
RACK #5 POWER
L1
N
208/120VAC
20A/1P
L2
L3
3 PHASE
RACK #6 POWER
L1
N
208/120VAC
L2
L3
3 PHASE
OPTION
208V 3 PHASE RACK CONNECTION
5
11
9
7
13
12
14
10
8
6
OPTION
3
4
208V 1 PHASE RACK CONNECTION
20A/1P
RACK #1 POWER
L2
208 1 PHASE
L3
23
24
20A/1P
RACK #2 POWER
208 1 PHASE
20A/1P
RACK #3 POWER
L1
208 1 PHASE
L2
20A/1P
RACK #4 POWER
208 1 PHASE
20A/1P
RACK #5 POWER
L3
208 1 PHASE
L1
20A/1P
RACK #6 POWER
208 1 PHASE
11
9
13
12
14
10
L2
L3
L1
L2
L3
L1
5
7
8
6
OPTION
3
4
120V 1 PHASE RACK CONNECTION
20A/1P
20A/1P
RACK #2 POWER
H
N
120VAC 1 PHASE
RACK #1 POWER
H
N
120VAC 1 PHASE
RACK #4 POWER
H
N
120VAC 1 PHASE
RACK #3 POWER
H
N
120VAC 1 PHASE
RACK #6 POWER
H
N
120VAC 1 PHASE
RACK #5 POWER
H
N
120VAC 1 PHASE
10A/1P
20A/1P
20A/1P
20A/1P
LIEBERT
HVAC UNIT
L1
L2
L3
G
208,240, OR 460VAC
L2
L1
60Hz
3
L3
G
LIEBERT
OPTIONAL REDUNDANT
L1
L2
L3
G
L2
L1
60Hz
3
L3
G
HVAC UNIT
LIEBERT COOLING POWER
CONNECTIONS
208,240, OR 460VAC
CUSTOMER PROVIDED
DCR-PD-3
3Ø PANELBOARD
15A/1P
1
3
5
11
9
7
17
15
13
23
21
19
24
18
22
12
14
16
10
8
6
4
2
20
29
27
25
30
28
26
208/120VAC
L1
60Hz
3
15A/1P
FIRE SUPPRESSION
CONTROL SYSTEM
H1
H2
CHASSIS GROUND
CONTROL PANEL
1
2
CHASSIS GROUND
TB1
REMOVE WIRES
IF USING UPS
OPTION
(INTERNAL BATTERY BACK-UP)
35
33
31
36
34
32
41
39
37
42
40
38
L2
L3
N
G
NOTE: CONTROL LOGIC
MUST BE BACKED BY
OPTION
42P
ON-LINE DOUBLE
CONVERSION UPS-SOURCE
1 OF 1
3PH Load Distribution Center
Содержание SmartRow DCR
Страница 1: ...SmartRow DCR 3 to 6 Rack 20 kW N N 1 and 5 to 10 Rack 36 kW N Cooling Units 60 Hz Installer User Guide...
Страница 6: ...Vertiv SmartRow DCR Installer User Guide 6...
Страница 12: ...Vertiv SmartRow DCR Installer User Guide 12 This page intentionally left blank...
Страница 52: ...Vertiv SmartRow DCR Installer User Guide 52 This page intentionally left blank...
Страница 66: ...Vertiv SmartRow DCR Installer User Guide 66 This page intentionally left blank...
Страница 70: ...Vertiv SmartRow DCR Installer User Guide 70 This page intentionally left blank...
Страница 72: ...Vertiv SmartRow DCR Installer User Guide 72 This page intentionally left blank...
Страница 76: ...Vertiv SmartRow DCR Installer User Guide 76 This page intentionally left blank...
Страница 82: ...Vertiv SmartRow DCR Installer User Guide 82 This page intentionally left blank...
Страница 101: ......