Figure 4.28 Adjust cover plates, place and attach emergency-fan assembly
NO.
DESCRIPTION
1
Cover plates
2
Cover plates with holes for screws
3. Plug the emergency fans into outlets on the adjacent Emergency-fan housing as shown in
Figure 4.29 below. Ensure that all fans are daisy-chained to each other.
4. Plug the emergency fan on the rack next to the PDX/PCW into the receptacle
on top of the Top Plenum-PDX/PCW, Figure 4.29.
Figure 4.29 Connect Emergency Fans
NO.
DESCRIPTION
1
Power connection for adjacent emergency fan
2
Power cord
3
Power connection on top plenum of PDX/PCW
Vertiv
| SmartRow DCR Installer/User Guide |
45