MNL000449.doc
Revision 22
02/15/2019
Gasguard Distribution
© Versum Materials, Inc. as of the revision and date shown. All rights reserved.
Confidential and Proprietary Data
Page
10
-
8
Versum Materials Confidential
Component Expected Life
This section provides the expected life of several system components. The
listed expected life is the length of time during which the component, with
proper care and handling as outlined in Section 10.2, is expected to function
properly. At the end of the expected life, the component should be replaced to
ensure the safe and proper functioning of the system.
Mechanical Components Expected Life
Component
Expected Life / Recommended Minimum
Changeout Frequency
Pressure Transducers
10 years
Process Regulator
Diborane: 2 years
Corrosives: 5 years
All others: 10 years
Purge Regulator
10 years
Excess Flow Switch
10 years
Valves
10 years
Pressure Transducers
10 years
Valves
10 years
Vacuum Venturi
10 years
Exhaust Ventilation Inlet Filter
10 years
Analog Exhaust Monitor
10 years
Exhaust Switch
2 years
Pneumatic Fittings
5 years
Pneumatic Tubing
Outdoor: 2 years
Indoor: 10 years
UV/IR Detector
10 years
UV source for auto self-check
3 years
Temperature Switch
10 years
Pressure Switch (Coaxial Tubing)
10 years