8.8.12 Analog Scaling
The Analog Scaling window will display all the analogs used in the system. The
operator will be allowed to choose an analog or exit the window. After selecting
an analog, the operator can change the maximum and minimum scaling values
using the keypad. The Analog Scaling window will display the analog number,
analog label, device type (milliamps or volts), minimum analog value, and
maximum analog value for each analog point. This window will allow the
operator to exit the window or enter a new analog range minimum and/or analog
range maximum for one or more analog points. To change the analog scaling
values, select the input of your choice by touching the screen. Select either the
minimum or maximum. Use the keypad to type in a numeric value. Press
to accept the changes. Press the
pushbutton to exit the window.
Apply
OK