KSTDV Series Gas Fireplace
VENTING INSTALLATION
VERTICAL SIDEWALL INSTALLATION
NOTE: Sealant is not required to assemble fi replace
venting. Do not use silicone sealant at the inner fl ue
exhaust connections.
Step 1
Locate vent opening on the wall. It may be necessary to
fi
rst position the
fi
replace and measure to obtain hole lo-
cation. Depending on whether the wall is combustible or
noncombustible, cut opening to size.
Figure 11
(For com-
bustible walls
fi
rst frame in opening.)
Combustible Walls:
Cut a 10
1
⁄
2
”H x 10
1
⁄
2
”W (267 x 267
mm) hole through the exterior wall and frame as shown.
Figure 11
Noncombustible Walls:
Hole opening must be 8
1
⁄
2
” (216
mm) in diameter.
Vent Opening for Combustible Walls
10
1
⁄
2
”
(267 mm)
Min.
Fireplace Hearth
Framing Detail
Opening for Noncombustible Wall
8
1
⁄
2
"
(216 mm)
Fireplace Hearth
Figure 11 -
Locate vent opening on wall
10
1
⁄
2
"
(267 mm) Min.
Step 2
Secure
fi
restop to the inside frame, center in the
10
1
⁄
2
" x
10
1
⁄
2
" vent opening.
Step 3
Place
fi
replace into position. Measure the vertical height
(X) required from the base of the
fl
ue collars to the center
of the wall opening.
Figure 12
Step 4
Using appropriate length of pipe section(s) attach to
fi
re-
place with three (3) screws. Follow with the installation of
the elbow.
Step 5
Measure the horizontal length requirement
fi
guring a 1
1
⁄
4
”
(32 mm) overlap, i.e. from the elbow to the outside wall
cap.
Figure 13
X
Figure 12 -
Vertical Height
Requirement
X
Figure 13 -
Horizontal Length
Requirement
FP1385
Always install horizontal venting on a level
plane.
Step 6
Use appropriate length of pipe sections - telescopic or
fi
xed - and install.
Sealing vent pipe and fi restop gaps with high tem-
perature sealant will restrict cold air being drawn in
around fi replace.
Step 7
Guide the vent terminations 5” and 8” collard into their
respective vent pipes. Double check that the vent pipes
overlap the collars by a minimum of 1
1
⁄
4
" (32 mm). Secure
the termination to the wall with screws provided and caulk
around the wall plate to weatherproof. As an alternative to
screwing the termination directly to the wall, you may also
use expanding plugs or an approved exterior construction
adhesive.
Support horizontal pipes every 36” (914
mm) with metal pipe straps.
For models purchased after 4/16/15, please see addendum.