KSTDV Series Gas Fireplace
CHECK GAS PRESSURE
1. Check gas type. The gas supply must be the same as
stated on the appliance’s rating decal. If the gas supply
is different from the
fi
replace,
STOP!
Do not install the
appliance. Contact your dealer immediately.
2. To ease installation, a 24" (610 mm)
fl
ex line with manual
shut-off valve has been provided with on this appliance.
Install and attach 1/2" gas line onto shut-off valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to the
fi
replace for leaks. Use a solution of 50/50 water and
soap solution or a gas sniffer.
4. To check gas pressures at valve, turn captured screw
counter clockwise 2 or 3 turns and then place tubing
to pressure gauge over test point. Turn unit to high.
Figure 29.
After taking pressure reading, be sure and
turn captured screw clockwise
fi
rmly to reseal. Do not
over torque. Check test points for gas leaks.
ELECTRICAL WIRING
General
1. This
fi
replace is equipped with the Signature Control
valve which operates on 6 volts. The AC module plugs
into the
fi
replace junction box A/C power supply. Four
(4) “AA” batteries are used for back up during power
outages.
2. The Signature Command System can also be operated
without A/C power. The system can run on four (4) “AA”
batteries for approximately six (6) months under normal
use.
3. A/C power must be used to power the A/C module,
blowers, lights and AUX accessories used with this
fi
replace.
Optional Accessory Requirements
1. This
fi
replace may be used with a wall switch and/or
Signature Command wireless controls.
2. The command center control may be mounted on the
wall with the use of the SCSWEK 15ft. wall mount
extension kit.
Figure 29 -
Signature Command Valve
W
ARNING
Do not use open fl ame to check for gas
leaks.
Pilot Adjustment
Screw
Pressure Outlet
FP1909a
Pressure Inlet
CHECKING GAS PRESSURE AND ELECTRICAL INSTALLATION
W
ARNING
E l e c t r i c a l c o n n e c t i o n s s h o u l d o n l y
be performed by a qualified, licensed
electrician. Main power must be off when
connecting to main electrical power supply
or performing service. All wiring shall be
in compliance with all local, city and state
codes. The appliance, when installed, must
be electrically grounded in accordance with
local codes or in the absence of local codes,
with the National Electrical Code ANSI/NFPA
70 (latest edition) and Canadian Electrical
Code, CSA C22.1.
CAUTION
Label all wires before disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.