KSTDV Series Gas Fireplace
VENTING INSTALLATION
INSTALLATION PRECAUTIONS
Consult local building codes before beginning the
installation. The installer must make sure to select the
proper vent system for installation. Before installing vent
kit, the installer must read this
fi
replace manual and vent
kit instructions.
Only a quali
fi
ed installer/service person should install the
venting system. The installer must follow these safety rules:
•
Wear gloves and safety glasses for protection.
•
Use extreme caution when using ladders or when on
rooftops.
•
Be aware of electrical wiring locations in walls and
ceilings.
The following actions will void the warranty on your venting
system:
•
Installation of any damaged venting component.
•
Unauthorized modi
fi
cation of the venting system.
•
Installation of any component part not manufactured or
approved by Vermont Castings Group
•
Installation other than permitted by these instructions.
This fi replace must be vented to the outside.
The venting system must NEVER be attached
to a chimney serving a separate solid fuel
burning appliance. Each gas appliance must
use a separate vent system. Do not use
common vent systems.
W
ARNING
Read all instructions completely and
thoroughly before attempting installation.
Failure to do so could result in serious
injury, property damage or loss of life.
Operation of improperly installed and
maintained venting system could result in
serious injury, property damage or loss of
life.
W
ARNING
Failure to follow these instructions will
void the warranty.
NOTICE
*3”
**1”
**1”
24”
(610 mm)
72”
(1829 mm)
Figure 7 -
Combustible Clearances for Vent Pipe
* A minimum of 3" clearance to the top is required along
horizontal length until
fl
ue pipe penetrates outside wall.
** A minimum 1" clearance to combustibles permitted all
around
fl
ue at outside wall
FP2567
W
ARNING
Horizontal sections of this vent system
require a minimum of 3" clearances to
combustibles at the top of the fl ue and 1"
clearance at the sides and bottom until the
fl ue penetrates the outside wall. A minimum
1" clearance all around the fl ue is acceptable
at this point of penetration. Unless the
vertical run is 7
1
⁄
2
feet or higher from fl oor
of fi replace, the clearance for horizontal run
is 1" on all sides.
Vertical sections of this vent system require
a minimum of 2" clearance to combustibles
at the top of the unit directly above the
stand-off. A minimum of 1" clearance all
around the fl ue is acceptable thereafter.
For models purchased after 4/16/15, please see addendum.