5
20307393
5" x 8" DVP Termination Kit
Secure the Vent Sections
Vertical secitons of pipe must be supported every 8 ft. after
the 25 ft. maximum unsupported rise. The vent support or
plumber’s strap (spaced 120° apart) may be used to do
this (see Figure 7).
Horizontal sections of vent must be supported every 5 ft
with a vent support or plumber’s strap. (See Figure 8)
DISASSEMBLE VENT SECTIONS
To disassemble any two pieces of pipe, rotate either section
(Figure 9), so that the seams on both pipe sections are
aligned (Figure 10). They can then be carefully pulled apart.
Figure 7 Securing Vertical Pipe Sections
Figure 8 Securing Horizontal Pipe Sections
Figure 10 Align and Disassemble Vent Sections
Figure 9 Rotate Seams for Disassembly
INSTALL HORIZONTAL TERMINATION CAP
Note: For horizontal vent runs through a
combustible wall and framing dimensions, refer
to appliance installation manual.
WARNING
Risk of Fire/Explosion/Asphyxiation! Improper support
may allow vent to sag and separate. Use vent run
supports and connect vent sections per installation
instructions. DO NOT allow vent to sag below connection
point to appliance.
WARNING
Risk of Fire! The telescoping flue section of the
termination cap MUST be used when connecting vent.
• 1
1
⁄
2
" (38 mm) minimum overlap of vent and tele-
scoping flue section is required.
Failure to maintain overlap may cause overheating and
fire.