KSTDV Series Gas Fireplace
GAS PIPE INSTALLATION
CHECK GAS TYPE
Use proper gas type for the
fi
replace you are installing.
If you have con
fl
icting gas type, do not install
fi
replace.
See dealer where you purchased the
fi
replace for proper
fi
replace according to your gas type.
When using copper or
fl
ex connectors use only
fi
ttings
approved for gas connections. The gas control inlet is
3/8" NPT.
CAUTION
For propane/LP units, never connect
fi replace directly to the propane/LP supply.
This burner system requires an external
regulator (not supplied). Install the external
regulator between the burner system and
propane/LP supply.
INSTALLATION ITEMS NEEDED
Before installing
fi
replace and burner system, make sure
you have the items listed below.
•
External regulator
•
Tee
joint
•
Test gauge connection*
•
Pipe
wrench
•
Sediment trap (recommended)
•
Equipment shutoff valve*
•
Piping (check local codes)
•
Sealant (resistant to propane/LP gas) (supplied by
installer)
•
approved
fl
exible gas line with gas connector (if
allowed by local codes — not provided)
* A CSA design-certi
fi
ed equipment shutoff valve with
1/8" NPT tap is an acceptable alternative to test gauge
connection. Purchase the CSA design-certi
fi
ed equip-
ment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply
an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas
pressure to between 11 and 13 inches of water. If you do
not reduce incoming gas pressure, burner system regulator
damage could occur. Install external regulator with the vent
pointing down as shown in
Figure 27.
Pointing the vent
down protects it from freezing rain or sleet.
CAUTION
Use only new black iron or steel pipe.
Internally tinned copper or copper tubing
can be used per National Fuel Code, Section
2.6.3, providing gas meets hydrogen sulfi de
limits, and where permitted by local codes.
Gas piping system must be sized to provide
minimum inlet pressure (listed on data plate)
at the maximum fl ow rate (BTU/hr). Undue
pressure loss will occur if the pipe is too
small.
External
Regulator
100 gal. (min)
Propane/LP
Supply Tank
Vent Pointing
Down
Figure 27 -
External Regulator with Vent Pointing Down (Propane/LP
Only)
FP1977
A qualifi ed installer or service person must
connect appliance to gas supply. Follow
all local codes.
W
ARNING
External regulators may be necessary for
natural gas. One- or two-pound systems
will damage this appliance and may cause
fi re hazard.
W
ARNING