3-3
7.1
95-8533
Determining Power Requirements
Tables 3-1 and 3-2 are provided for calculating the
total current requirements for those parts of the
system requiring battery backup.
Table 3–1—
Standby Current Requirements at 24 vdc
Device Type
Number of Devices
Standby Current
Total Current for Device Type
EQP Controller
X
0.360
=
EDIO Module
X
0.075
=
DCIO Module
X
0.075
=
Power Supply. Monitor
X
0.060
=
IDC/IDCGF/IDCSC
X
0.055
=
X3301/X3301A - w/o heater
X
0.160
=
X3301/X3301A - with heater
X
0.565
=
X3302 - without heater
X
0.160
=
X3302 - with heater
X
0.565
=
X2200
X
0.135
=
X9800 - without heater
X
0.085
=
X9800 - with heater
X
0.420
=
X5200 - without heater
X
0.155
=
X5200 - with heater
X
0.490
=
DCUEX
X
0.145
=
DCU with EC Sensor
X
0.060
=
DCU with PointWatch
X
0.300
=
DCU with DuctWatch
X
0.300
=
Relay Module
X
0.120
=
Analog Input Module
X
0.160
=
Intelligent Protection Module
X
0.075
=
EQ2220GFM
X
0.018
=
PIRECL
X
0.270
=
OPECL Transmitter
X
0.220
=
OPECL Receiver
X
0.220
=
ARM
X
0.075
=
SAM
X
0.060
=
Network Extender
X
0.090
=
EQ21xxPS Power Supply
X
0.350
=
Other
X
=
Total
Standby Current for System (in amperes)
=
Note: Standby current is the average current draw for the device in normal mode.
This table is for battery calculations only.
Содержание DET-TRONICS 95-8533
Страница 1: ...Instructions 95 8533 Eagle Quantum Premier Fire and Gas Detection Releasing System 7 1 9 09 95 8533 ...
Страница 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Страница 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Страница 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Страница 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Страница 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Страница 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Страница 143: ...APPENDIX E E 1 95 8533 7 1 ...