7.1
NOTE
FM Approval allows the presence and operation of serial communications software in the Controller (MODBUS,
Allen Bradley protocols, etc.); however, the communications functions are not included in the Approval.
95-8533
A-2
Table A-1—Circuit Classifications
signaling Path
nfPa 72 supervision
Local Operating Network (LON)
Signaling Line Circuit (SLC): Class A, Style 7
Power Distribution Module, Input Power
Supervised. Loss of power per ANSI/NFPA 72, Cl. 1-5.8.7.
Power Distribution Module, Controller Power Output
Supervised. Loss of power per ANSI/NFPA 72, Cl. 1-5.8.7.
Power Distribution Module, Field Device Power Output
Supervised. Single open or ground-fault per ANSI/NFPA 72, Cl. 1-5.8.
Power Distribution Module, Local Field Device Power Output
Unsupervised per ANSI/NFPA 72, Cl. 1-5.8, Exception #7 & #8.
Power Supply Monitor, Input Power
Supervised. Loss of power per ANSI/NFPA 72, Cl. 1-5.8.7.
Power Supply Monitor, Output Power
Supervised (via Controller for opens).
Single open or ground-fault per ANSI/NFPA 72, Cl. 1-5.8.
Power Supply Monitor, Charger
Supervised. Loss of charger per NFPA Cl. 1-5.2.9.5.
Power Supply Monitor, Battery
Supervised. Loss of battery per NFPA Cl. 1-5.8.7.
Controller, Digital Input
Unsupervised per ANSI/NFPA 72, Cl. 1-5.8, Exception #7 & #8.
Controller, Relay Output
Unsupervised per ANSI/NFPA 72, Cl. 1-5.8, Exception #7 & #8.
Controller, Trouble Relay Output
Unsupervised per ANSI/NFPA 72, Cl. 1-5.8, Exception #7 & #8.
Controller, 232 Expansion Output (SIL or Non-SIL)
Unsupervised per ANSI/NFPA 72, Cl. 1-5.8, Exception #7 & #8.
Controller, SLC485 Expansion Output, including
Class B, Style 4 (Single Channel Single-Mode Fiber)
optional fiber optic equipment (SIL or Non-SIL)
Class A, Style 7 (Multi-Mode Fiber or Dual Channel Single-Mode Fiber
or Dual Channel Wire)
Redundant Controller Connector, RS-232 (SIL or Non-SIL) Unsupervised per ANSI/NFPA 72, Cl. 1-5.8, Exception #7 & #8.
Relay Module, Output
Unsupervised, for connection with ancillary equipment only.
Enhanced Discrete I/O, Input (software configurable)
Unsupervised per ANSI/NFPA 72, Cl. 1-5.8, Exception #7 & #8.
Initiating Device Circuit (IDC): Class A, Style D
Initiating Device Circuit (IDC): Class A, Style E
Initiating Device Circuit (IDC): Class B, Style B
Initiating Device Circuit (IDCSC): Class B, Style C
Enhanced Discrete I/O, Output (software configurable) Unsupervised per ANSI/NFPA 72, Cl. 1-5.8, Exception #7 & #8.
Notification Appliance Circuit (NAC): Class A, Style Z
Notification Appliance Circuit (NAC): Class B, Style Y
Supervised Solenoids (Class A or Class B):
Single open or ground-fault per ANSI/NFPA 72, Cl. 1-5.8.
Group B: ASCO T8210A107
Group D: ASCO 8210G207
Group E: Skinner 73218BN4UNLVNOC111C2
Group F: Skinner 73212BN4TNLVNOC322C2
Group G: Skinner 71395SN2ENJ1NOH111C2
Group H: Viking HV-274-060-7
Содержание DET-TRONICS 95-8533
Страница 1: ...Instructions 95 8533 Eagle Quantum Premier Fire and Gas Detection Releasing System 7 1 9 09 95 8533 ...
Страница 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Страница 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Страница 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Страница 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Страница 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Страница 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Страница 143: ...APPENDIX E E 1 95 8533 7 1 ...