3-51
7.1
95-8533
EQ25XXARM SERIES AGENT RELEASE MODULE
Mounting
The device should be securely mounted to a vibration
free surface. (See “Specifications” in this manual for
device dimensions.)
Wiring
To ensure proper operating voltage for the output
device, the maximum wiring length from power source
to device must not exceed the values shown in Table
3-19 for automatic release applications or Table 3-20
for deluge and pre-action applications.
NOTe
For solenoids, this wire length includes both the
wiring from power supply to device, and the
wiring from device to solenoid. For squibs, use
only the wire length from power supply to
module, since the resistance of the wire from
module to squib is included when determining
the value of the compensating resistor.
See Figure 3-67 for identification of wiring terminals.
Terminals 1 to 4 —
Output terminals
Connect a single solenoid
between terminals 1 and 4.
Connect dual solenoids
between terminals 1 and 2,
and between terminals 3 and
4.
NOTe
For testing purposes, a load resistor of 1200 to
1500 ohms @ 1 watt can be placed across
terminals 1 and 4.
When using an explosive
initiator, connect the resistor
between terminals 1 and 2
and the initiator between
terminals 3 and 4, as shown
in Figure 3-67.
CAUTION!
DO NOT intermix different types of initiators in
release circuit.
Terminals 5 to 10 —
LO N s i g n a l i n g c i rc u i t
terminals
NOTe
Be sure to observe polarity when wiring the
LON.
5 — “A” side of signaling
circuit for COM 2
6 — “B” side of signaling
circuit for COM 2
7 and 8 —
s h i e l d
connections
9 — “A” side of signaling
circuit for COM 1
10 — “B” side of signaling
circuit for COM 1
Terminals 11 to 14 — 24 vdc power input
Connect module power
supply to terminals 12 and
13.
NOTe
If an auxiliary output supply is used for powering
solenoids, it should be connected to terminals 11
and 14.
Table 3-19—Maximum Wiring Length for Automatic Release
Applications
Device
Maximum Wire Length in Feet
12 AWG 14 AWG 16 AWG 18 AWG
890181*
150
100
60
899175*
150
100
60
895630*
150
100
60
897494*
190
120
75
486500*
1500
1000
600
400
31-199932-004*
150
100
60
Squib
190
120
75
2 Amp Load
190
120
75
*Fenwal Solenoid
Содержание DET-TRONICS 95-8533
Страница 1: ...Instructions 95 8533 Eagle Quantum Premier Fire and Gas Detection Releasing System 7 1 9 09 95 8533 ...
Страница 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Страница 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Страница 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Страница 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Страница 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Страница 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Страница 143: ...APPENDIX E E 1 95 8533 7 1 ...