95-8533
7.1
D-2
equip. no.
equipment type
manufacturer
Series/model description
16
THD-7052
Heat Detector
Fenwal
Uses 2-wire base 2WRLT.
17
CPD-7054 Ionization
Type Smoke Detector
Fenwal
Uses 2-wire base 2WRLT.
18
PSD-7157 and
PSD-7157D
Photoelectric Type
Smoke Detectors
Fenwal
Uses 2-wire base 2WRLT.
19
MT-12/24-R Horn
Fenwal
24 V dc model; installed in Fenwal IOB-R box.
20
MTWP-2475W – FR
Horn/Strobe
Fenwal
Multitone Weatherproof Horn-Strobe;
installed in Fenwal IOB-R box.
21
Manual Call Stations
Series 3300
Fenwal
Model 84-330001-002 pull station;
uses Fenwal SGB-32S interior surface mount backbox
(compatible mounting with B-11).
22
RA-911 Remote
Indicator
Fenwal
Remote indicator for use with Fenwal Heat
or Smoke detectors.
23
Manual Fire Alarm Call
Point PB Range
MEDC (UK)
Model PB-UL-4C-6C-4-DC-D-7-R call point
24*
CCH ETH 2416 Horn
Cooper Crouse Hinds
Uses CCH EAJC26 conduit outlet box with cover,
3/4 NPT hub size.
25
AST-4-1030 Strobe
Applied Strobe
Technology (Canada)
AST-4-10-30-DC-CL-CM-75-ULC;
with clear lenses
26
SL-2000-P
Duct Smoke Detector
Air Products &
Controls
SL-2000-P; installed in Hoffman LWC204015SS6
NEMA 4X enclosure; uses Apollo 55000-328A
photoelectric head w/ RW-268A base.
Table D-1— List of Approved Equipment (Continued)
IMPORTANT
The EQP2120PS-B Power Supplies provide EQP System devices with power from input supply 120 to 220 V ac.
The EQP2120PS-B Power Supplies are used in pairs where primary source of input supply is connected to one
and the secondary source is connected to the other. Use of this power supply does not provide the source of the
secondary supply such as secondary source batteries, their supervision or charging, or UPS. Per NFPA 72-2002
requirements, such power supply related requirements must be separately provided for and be accepted by the
local Authority Having Jurisdiction (AHJ).
HAzArdouS LocAtionS
Refer to Figure D-1 (Drawing 007545-001) for System Classification details.
SyStem SpecificAtion
EQP2120PS-B POWER SUPPLY—
number of units:
16 (8 pairs) max
input voltage:
120 – 220 Vac - 15% + 10%, 60/50 Hz single phase
output voltage
:
Nominal–
24.5 Vdc ± 1% Vdc
Range–
24.5….28.0 Vdc
input current
:
Vout = 24.5 Vdc:
4.9 Amps @ 120 Vac
2.9 Amps @ 220 Vac.
Vout = 28.0 Vdc:
5.6 Amps @ 120 Vac
3.2 Amps @ 220 Vac.
output current, each
:
20 A
*Horn item 24 is for use in gas applications only.
Содержание DET-TRONICS 95-8533
Страница 1: ...Instructions 95 8533 Eagle Quantum Premier Fire and Gas Detection Releasing System 7 1 9 09 95 8533 ...
Страница 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Страница 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Страница 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Страница 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Страница 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Страница 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Страница 143: ...APPENDIX E E 1 95 8533 7 1 ...