7.1
3-18
95-8533
Use Port 2 to pass safety critical information between
controllers. User logic can pass all alarm, trouble,
and supervisory information between the controllers.
Watchdog timers must be implemented in user logic
to verify the integrity of the SLC. Consult the local
authority having jurisdiction for annunciation
requirements.
CONTROLLER TO CONTROLLER COMMUNICATION
Controller to Controller Communication (SLC485)
with Signaling Line Circuit Classification Class A
or B, per NFPA 72
To connect up to twelve controllers together and be
able to transfer safety information between the
controllers, the communication link must be classified
as a signaling line circuit per NFPA 72. With the serial
board option, Port 2 (plug 10) is a RS-485 serial
connection that is ground fault monitored.
To meet the signaling line circuit (Class A, Style 7) or
(Class B Style 4) requirements, the following must be
configured for correct operation:
• All controllers must have the optional serial board.
• The Termination jumper P28 must be set to
Terminate (position 1-2) on all controllers.
• The Ground Fault Monitor jumper P29 must be set to
Enabled (position 1-2) on all controllers.
• For Class A, Connect terminals A (# 56) and B (# 55)
between the controllers. Connect terminal A (# 60) and
B (# 61) between controllers using a different cable route.
Connect GND (# 54) to GND (# 62) on each controller.
• For Class B, connect terminals A (terminal number
60) and B (terminal number 61) between the
controllers. The GND (terminal number 62) must not
be connected.
See Figure 3-13 for wiring details.
Note 1: 56.7 kbps minimum and 115.2 kbps maximum
baud rate required for proper communication.
Note 2: Consult the factory for configuration set-up.
Note 3: Maximum SLC485 length over copper not to
exceed 1000 meters.
Controller to Controller with Fiber Optic Link, Signal
Line Circuit Classification Class A or B per NFPA 72.
Up to twelve EQP controllers (single or redundant
pair) can be inter-connected via a fiber optic link. This
communication link is classified as a signaling line
circuit per NFPA 72 to allow safety information to be
transferred between controllers.
60
62
61
61
63
65
64
67
64
67
66
68
P28: RS-485 Termination Jumper,
Position 1 & 2
P29: RS-485 Ground Fault
Monitor Jumper, Position 1 & 2
A
B
P28
1
3
P29
1
3
P12
PORT 4
P11
PORT 3
P10
PORT 2
60
62
63
65
66
68
P28: RS-485 Termination Jumper,
Position 1 & 2
P29: RS-
485 Ground Fault
Monitor Jumper, Position 1 & 2
A
B
P28
1
3
P29
1
3
P12
PORT 4
P11
PORT 3
P10
PORT 2
GND
A
B
GND
A
B
D2276
TO
ADDITIONAL
CONTROLLER(S)
54
55
56
54
55
56
EAGLE QUANTUM PREMIER
Safety System Controller
Fire Alarm
Inhibit
Power
Supr
High Gas
Trouble
Cntrl Flt
Lon Fault
Low Gas
Ack
Silence
Out Inhibit
Eagle Quantum Premier
Time & Date
Cancel
Enter
Next
Previous
Reset
Acknowledge Silence
DET
-
TRONICS
®
EAGLE QUANTUM PREMIER
Safety System Controller
Fire Alarm
Inhibit
Power
Supr
High Gas
Trouble
Cntrl Flt
Lon Fault
Low Gas
Ack
Silence
Out Inhibit
Eagle Quantum Premier
Time & Date
Cancel
Enter
Next
Previous
Reset
Acknowledge Silence
DET
-
TRONICS
®
Figure 3-13—Controller to Controller Communication with Class A Signaling Line Circuit Classification per NFPA 72
Содержание DET-TRONICS 95-8533
Страница 1: ...Instructions 95 8533 Eagle Quantum Premier Fire and Gas Detection Releasing System 7 1 9 09 95 8533 ...
Страница 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Страница 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Страница 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Страница 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Страница 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Страница 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Страница 143: ...APPENDIX E E 1 95 8533 7 1 ...