7.1
95-8533
6-14
cErTIfIcATION—
FM / CSA:
Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class II/III, Div. 1, Groups E, F, G.
Class I, Div. 2, Groups A, B, C, D (T4A).
Class I, Zone 2, Group IIC (T4 ).
Class II/III, Div. 2, Groups F & G (T4A).
NEMA/Type 4X.
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
CENELEC/CE: ATEX/EMC Directive Compliant.
0539
FM
®
II 2 G
EEx d IIC T4-T6
DEMKO 02 ATEX 131321X
T6 (Tamb = –55°C to +50°C).
T5 (Tamb = –55°C to +65°C).
T4 (Tamb = –55°C to +75°C).
IP66.
Special conditions for Safe Use (X):
The device has an ambient temperature rating for
performance of –40°C to +75°C.
Refer to Appendix C for CE Mark details.
EQ24xxNE NETWORK EXTENDER
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will
not cause damage to the equipment.
POwEr cONSUmPTION—
2.2 watts nominal at 24 vdc, 2.7 watts maximum.
INPUTS/OUTPUTS—
Digital, transformer isolated (78.5k Baud).
TEmPErATUrE rANGE—
Operating: –40°F to +167°F (–40°C to +75°C)
Storage:
–67°F to +185°F (–55°C to +85°C).
HUmIdITY—
5 to 95% RH at 70°C.
dImENSIONS—
See Figure 6-7.
cErTIfIcATION—
FM / CSA:
Class I, Div. 1, Groups B, C, D.
Class I, Zone 1, Group IIC.
Class II/III, Div. 1, Groups E, F, G.
Class I, Div. 2, Groups A, B, C, D (T4A).
Class I, Zone 2, Group IIC (T4 ).
Class II/III, Div. 2, Groups F & G (T4A).
NEMA/Type 4X.
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
CENELEC/CE: ATEX/EMC Directive Compliant.
0539
FM
®
II 2 G
EEx d IIC T4-T6
DEMKO 02 ATEX 131321X
T6 (Tamb = –55°C to +50°C).
T5 (Tamb = –55°C to +65°C).
T4 (Tamb = –55°C to +75°C).
IP66.
Special conditions for Safe Use (X):
The device has an ambient temperature rating for
performance of –40°C to +75°C.
Refer to Appendix C for CE Mark details.
Refer to Appendix D for USCG Approval details.
A1883
0.32 (0.81) OVAL SLOT MOUNTING
(TYPICAL FOUR PLACES)
3.39
(8.6)
4.66
(11.8)
3.7
(9.4)
5.20
(13.21)
0.28
(0.71)
2.69
(6.83)
1.28
(3.25)
figure 6-7—dimensions of Short cover Junction box
in Inches (centimeters)
Содержание DET-TRONICS 95-8533
Страница 1: ...Instructions 95 8533 Eagle Quantum Premier Fire and Gas Detection Releasing System 7 1 9 09 95 8533 ...
Страница 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Страница 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Страница 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Страница 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Страница 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Страница 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Страница 143: ...APPENDIX E E 1 95 8533 7 1 ...