7.1
95-8533
4-17
EMBEDDED LOGIC – OPERATION
Supervisory Condition:
The supervisory input on
channel 3 has no embedded logic function and is
passed on as information only to the EQP Controller
where it is displayed as a supervisory fault.
Alarm Condition - Single Zone Mode:
Upon receipt
of an alarm from an activated detector on IPM channel
4 or 5 OR activation of the manual station, channel 2:
Signal circuit devices are activated per the software
selected signaling circuit configuration described
earlier – Bell Circuit Channel 6.
Programmed release time delay activated.
Release output(s) activated.
Operation of Abort: Discharge is aborted ONLY
when alarm is from a detector, and abort is
activated during programmed release time delay.
Abort sequence is dependent on the abort mode
selection as described earlier.
Alarm Condition – Two Zone Mode (cross zoned):
Upon receipt of an alarm from one activated detector
in one zone.
Signal circuit devices are activated per the software
selected signaling circuit configuration, two zone
mode, one zone in alarm, as described earlier –
Bell Circuit Channel 6.
Second Alarm Condition: Upon receipt of an alarm
from a second activated detector in the other zone.
Signal circuit devices are activated per the software
selected signaling circuit configuration, two zone
mode, two zones in alarm, as described earlier –
Bell Circuit Channel 6.
Programmed release time delay activated.
Release output(s) activated.
Manual Alarm Condition – Two Zone Mode (cross
zoned):
Upon receipt of a manual alarm from Channel 2:
Signal circuit devices are activated per the software
selected signaling circuit configuration, two zone
mode, two zones in alarm, as described earlier –
Bell Circuit Channel 6.
Programmed release time delay activated.
Release output(s) activated.
Module Reset:
After completion of the release
output(s) timer, if no alarm condition is present on
channel 2 (Manual Release) then the module can be
reset via soft command on the S3 Module Point
Display or if the EQP Controller is offline, by holding
the Abort input, Channel 1, active momentarily.
When reset, the IPM will de-energize the two detector
circuits, channels 4 and 5, for two seconds to reset
the smoke detectors. Any latched outputs will also be
reset.
Release Outputs:
When commanded to release, the
release output(s) will energize for the configured time
and then de-energize.
Содержание DET-TRONICS 95-8533
Страница 1: ...Instructions 95 8533 Eagle Quantum Premier Fire and Gas Detection Releasing System 7 1 9 09 95 8533 ...
Страница 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Страница 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Страница 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Страница 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Страница 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Страница 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Страница 143: ...APPENDIX E E 1 95 8533 7 1 ...